Detail Product :

SEW 890 PR Non-Contact Type Phase Sequence Indicators

Brand : SEW
Category : Pressure Meter

列印
  FEATURES
● The 890 PR is a Non-Contact phase detector
   with flashing LEDs and a beeping buzzer to
   show the detection of AC 3-phase sequence.
● Two functions in one unit : open phase and 
   phase sequence detection.
● Convenient brightness switch to make the
   indication visible in dim areas or sunlight.
● Back cover magnets which attach the instrument
   to the AC distribution panel offer easy
   measurement.   
● 3-Phase AC 70 to 1000V is fitted for detection.
● Conductor size: 1~35mm
● Detect frequency range is from 45 to 65Hz.
 
  SPECIFICATIONS
     
  Measurement principle   Static induction
  Input voltage   70~1000Vac
  Frequency range   45-65Hz
  Auto-off   5 min. after power on
  without detection
  Low battery warning   Power LED flashes at
  4.6±0.1V or less
  Operating temperature
  & humidity
 0°C ~ 40°C Max. 80% R.H.
  Storage temperature
  & humidity
  -10°C ~ 50°C Max. 80% R.H.
  Cable length   Approx. 800mm 
  Dimensions   115(L) × 65(W) × 40(D)mm
  Weight
  (battery included)
  Approx. 370g 
  Power source   1.5V (AA) × 4 Alkaline batteries
  Safety standard   EN 61010-1 CAT III  1000V /  CAT IV  600V
  EN 61326-1
  EN 61557-1  EN 61557-7

 

Untuk informasi lebih lanjut silahkan hubungi kami di nomor berikut :

WhatsApp